The LED will begin flashing in sequence to show the current chart rotation speed that is configured for the recorder:

Flash 1 time - 24 HOUR
Flash 2 times - 7 DAY

Without pressing the left (#1) or right (#2) buttons, press and release the "change chart" button (#3). The LED will turn solid green (stop flashing) and the pen(s) will begin to move off of the chart.

Once the pen(s) has moved off of the chart, the number one pen will move towards the outermost graduation of the chart and pause. If the pen does not move exactly to this location, you will have approximately five (5) seconds to adjust the pen's position using the left (#1) or right (#2) buttons. When the time to adjust the pen has expired, the second pen (on a two pen recorder) will move to the outermost graduation of the chart. You will have approximately five (5) seconds to adjust the second pen's position using the left (#1) or right (#2) buttons.

Once the pen(s) has been adjusted to the outermost graduation of the chart, the LED will begin flashing continuously. Once the LED has started flashing, press and release the right button (#2) to begin the span adjustment of the pen(s). The number one pen will move towards the innermost graduation of the chart and pause. If the pen does not move exactly to this location, you will have approximately five (5) seconds to adjust the pen's position using the left (#1) or right (#2) buttons. When the time to adjust the pen has expired, the pen will return to the outermost graduation of the chart.

Next, the second pen (on a two pen recorder) will move to the innermost graduation of the chart. You will have approximately five (5) seconds to adjust the second pen's position using the left (#1) or right (#2) buttons. When the time to adjust the second pen has expired, the pen will return to the outermost graduation of the chart and the recorder will resume normal operation.


A2

R70-32 (WEB)
REV(12-04) D